Alpha

Yudian Advanced Universal PID Controller-AI808

AI808

 

  • TECHNICAL SPECIFICATION
  • Input type: (Either of below specifications can be used selectively in the same instrument)
  • Thermocouple: K, S, R, E, J, N
  • Resistance temperature detector: Cu50, Pt100
  • Linear voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~20mV, etc.
  • Linear current (external precise shunt resist needed): 0~10mA, 1~20mA, 4~20mA, etc.
  • Extended input (install I4 module in MIO) : 0~20mA, 4~20mA or two line transmitter.
  • Optional: apart from the above-mentioned Input type, an additional type can be provided upon request. (Graduation
  • index is needed)
  • Instrument Input range
  • K(0~1300℃), S(0~1700℃), R(0~1700℃), E(0~1000℃), J(0~1200℃), N(0~1300℃)
  • K(32~2372℉), S(32~3092℉), R(32~3092℉), E(32~1832℉), J(32~2192℉), N(32~2372℉)
  • Cu50(-50~+150℃), Pt100(-200~+800℃)
  • Cu50(-58~+302℉), Pt100(-328~+1472℉)
  • Linear Input: -9990~30000 defined by user.
  • Measurement accuracy : 0.3%FS ± 0.1℃
  • Resolution : 0.1℃ for K, E, T, N, J, Cu50, Pt100; 1℃ for S, R
  • Temperature shift : ≤0.015%FS /℃ (typical value is 80ppm/℃)
  • Sampling period : read A/D converter 8 times per second
  • Response time : ≤0.5s ( when digital filter parameter FILt=0)
  • Alarm function : high limit, low limit, deviation high limit and deviation low limit; with alarm blocking at the beginning
  • of power on.
  • Control period : 0.5~120.0 seconds selectable, and it should be integer times of 0.5 second.
  • Control mode:
  • On-off control mode (deadband adjustable)
  • Standard PID with auto tuning
  • AI PID with auto tuning, adopting AI artificial intelligence algorithm.
  • Output mode (modularized)
  • Relay output (NO+NC): 250VAC/2A or 30VDC/1A
  • Servo motor output
  • TRIAC no contact discrete output (NO or NC): 100~240VAC/0.2A (continuous), 2A (20mS instantaneous, repeat
  • period≥5s)
  • SSR Voltage output: 12VDC/30mA (used to drive SSR).
  • Thyristor zero crossing trigger output: can trigger TRIAC of 5~500A, a pair of inverse paralleled SCRs or SCR
  • power module.
  • Linear current output: 0~20mA, 4~20mA (Output voltage ≥11V, maximum load resistor 500ohm, output
  • precision 0.2%FS)
  • Electromagnetic compatibility (EMC) : ±4KV/5KHz according to IEC61000-4-4; 4KV according to IEC61000-4-5.
  • Isolation withstanding voltage : between power, relay contact or signal terminal ≥2300VDC; between isolated
  • electroweak terminals ≥600VDC
  • Power supply : 100~240VAC, -15%, +10% / 50-60Hz; 120~240VDC; or 24VDC/AC, -15%, +10%.
  • Power consumption: ≤6W
  • Operating Ambient : temperature -10~60℃; humidity ≤90%RH
  • Front panel dimension: 96×96mm, 160×80mm, 80×160mm, 48×96mm, 96×48mm, 48×48mm, 72×72mm
  • Panel cutout dimension: 92×92mm, 152×76mm, 76×152mm, 45×92mm, 92×45mm, 45×45mm, 68×68mm
  • Depth behind mounting surface: 100mm

Control Equipments & Marketing Company. – The Complete Solution of Process Automation