Yudian Universal Indicator-AI500

- TECHNICAL SPECIFICATION
- Input type (field selectable) :
- Thermocouple: K, S, R, E, J, N
- Resistance thermometer: Pt100
- Linear voltage: 0~5V, 0~1V, 0~500mV, 0~100mV, 0~60mV, 0~20mV, etc.; 0~10V (with I3 module installed in MIO slot)
- Linear current (should connect a external resistor or install I4 module in MIO slot): 0~20mA, 4~20mA
- Linear resistor: 0~80 ohm, 0~400 ohm
- Measurement range :
- K(-100~+1300℃), S(0~1700℃), R(0~1600℃), E(0~1000℃), J(0~1200℃), N(0~1300℃),
- Pt100(-200~+800℃)
- Linear input : -9990~+30000 unit defined by user
- Measurement accuracy : 0.3%FS±1 unit
- Temperature display resolution : 0.1℃ for K, E, J, N, Pt100 and 1℃ for S, R
- Temperature shift : ≤0.015%FS/℃ (typical value is 75ppm/℃)
- Electromagnetic compatibility (EMC) : IEC61000-4-4, ± 4KV/5KHz; IEC61000-4-5, 4KV
- Retransmission : When X3 current module is installed in OUTP slot, process value (PV) can be retransmitted to standard current with maximum
- load resistor 500 ohm.
- Alarm function : High limit, low limit, and second high limit, second low limit.
- Isolation withstanding voltage : between power, relay contact or signal terminals ≥2300VDC; between isolated electroweak signal terminals≥
- 600VDC
- Power supply : 100~240VAC, -15%, +10% / 50-60Hz; 120~240VDC; 24VDC/AC, -15%, +10%.
- Power consumption: ≤5W
- Operating Ambient : temperature -10~+60℃; humidity ≤90%RH
- Front panel dimension: 96×96mm, 160×80mm, 80×160mm, 48×96mm, 96×48mm, 72×72mm, 48×48mm
- Panel cutout dimension: 92×92mm, 152×76mm, 76×152mm, 45×92mm, 92×45mm, 68×68mm, 45×45mm
- Depth behind mounting surface: ≤100mm
Control Equipments & Marketing Company. – The Complete Solution of Process Automation