Alpha

Yudian Universal Indicator-AI500

AI500

  • TECHNICAL SPECIFICATION
  • Input type (field selectable) :
  • Thermocouple: K, S, R, E, J, N
  • Resistance thermometer: Pt100
  • Linear voltage: 0~5V, 0~1V, 0~500mV, 0~100mV, 0~60mV, 0~20mV, etc.; 0~10V (with I3 module installed in MIO slot)
  • Linear current (should connect a external resistor or install I4 module in MIO slot): 0~20mA, 4~20mA
  • Linear resistor: 0~80 ohm, 0~400 ohm
  • Measurement range :
  • K(-100~+1300℃), S(0~1700℃), R(0~1600℃), E(0~1000℃), J(0~1200℃), N(0~1300℃),
  • Pt100(-200~+800℃)
  • Linear input : -9990~+30000 unit defined by user
  • Measurement accuracy : 0.3%FS±1 unit
  • Temperature display resolution : 0.1℃ for K, E, J, N, Pt100 and 1℃ for S, R
  • Temperature shift : ≤0.015%FS/℃ (typical value is 75ppm/℃)
  • Electromagnetic compatibility (EMC) : IEC61000-4-4, ± 4KV/5KHz; IEC61000-4-5, 4KV
  • Retransmission : When X3 current module is installed in OUTP slot, process value (PV) can be retransmitted to standard current with maximum
  • load resistor 500 ohm.
  • Alarm function : High limit, low limit, and second high limit, second low limit.
  • Isolation withstanding voltage : between power, relay contact or signal terminals ≥2300VDC; between isolated electroweak signal terminals≥
  • 600VDC
  • Power supply : 100~240VAC, -15%, +10% / 50-60Hz; 120~240VDC; 24VDC/AC, -15%, +10%.
  • Power consumption: ≤5W
  • Operating Ambient : temperature -10~+60℃; humidity ≤90%RH
  • Front panel dimension: 96×96mm, 160×80mm, 80×160mm, 48×96mm, 96×48mm, 72×72mm, 48×48mm
  • Panel cutout dimension: 92×92mm, 152×76mm, 76×152mm, 45×92mm, 92×45mm, 68×68mm, 45×45mm
  • Depth behind mounting surface: ≤100mm

Control Equipments & Marketing Company. – The Complete Solution of Process Automation